AeroElectric-List Digest Archive

Tue 03/03/20


Total Messages Posted: 7



Today's Message Index:
----------------------
 
     1. 11:08 AM - Test; List Server Issues... (Matt Dralle)
     2. 06:00 PM - Re: OV protection circuit design (Pat Little)
     3. 06:27 PM - Re: Re: OV protection circuit design (Charlie England)
     4. 06:41 PM - Re: Re: OV protection circuit design (Robert L. Nuckolls, III)
     5. 06:42 PM - Re: Re: OV protection circuit design (Robert L. Nuckolls, III)
     6. 07:53 PM - Re: Re: OV protection circuit design (Pat Little)
     7. 08:05 PM - Battery discharge during normal cruise (Paul Zimmer)
 
 
 


Message 1


  • INDEX
  • Back to Main INDEX
  • NEXT
  • Skip to NEXT Message
  • LIST
  • Reply to LIST Regarding this Message
  • SENDER
  • Reply to SENDER Regarding this Message
    Time: 11:08:34 AM PST US
    From: Matt Dralle <dralle@matronics.com>
    Subject: Test; List Server Issues...
    The Matronics Email List Server was having some issues and not accepting incoming posts for a couple of days. I think I have it resolved now. Sorry for the hassle. Matt Dralle Matt G Dralle | Matronics | 581 Jeannie Way | Livermore | CA | 94550 925-606-1001 V | 925-606-6281 F | dralle@matronics.com Email http://www.matronics.com/ WWW | Featuring Products For Aircraft


    Message 2


  • INDEX
  • Back to Main INDEX
  • PREVIOUS
  • Skip to PREVIOUS Message
  • NEXT
  • Skip to NEXT Message
  • LIST
  • Reply to LIST Regarding this Message
  • SENDER
  • Reply to SENDER Regarding this Message
    Time: 06:00:00 PM PST US
    From: Pat Little <roughleg@gmail.com>
    Subject: Re: OV protection circuit design
    On Thu, Feb 27, 2020 at 10:05 AM user9253 <fransew@gmail.com> wrote: > > I suggest buying a fuse block that holds 15 or 20 fuses. A builder once > said > to install a fuse block that holds twice as many fuses as you anticipate > needing, because you will need them. Every single load, no matter how > small, should have its own unique fuse. > Then replace the fuse-links with 30 amp fuses. Doing that will simplify > the > wiring. Looking at Z-20, I suspect the intent was two different wire > sizes, with > one a typo. If a 30 amp fuse is used instead of a fuse-link, then I would > use 22 > AWG for all wires in the field circuit. 22 AWG is good for 7 amps. It > takes 40 > amps to melt 22 wire. > Charlie, the alternator B lead is separate and not shown on the diagram. > > -------- > Joe Gores > I like the simplification of using fuses instead of fuselinks (my design has 22 fuses so far, another two won't be a problem). And I can appreciate that if an OV occurs, and the CB trips, the fuse needs to be big enough to not also blow and deny the pilot the chance to re-engage the breaker and see if the OV condition repeats itself or not. But why 30A? That seems very large as compared to a 5A CB. And a separate thought - if the fuse is significantly bigger, and its sole purpose is to protect the wire between the bus and the CB (am I interpreting this correctly?), then that segment of wire would need to be a lot bigger for the fuse to actually protect it. AC 43.13-1B says a 30A fuse is needed to protect a 10AWG wire - is this a valid reason for having differing wire sizes in different parts of the circuit? Pat


    Message 3


  • INDEX
  • Back to Main INDEX
  • PREVIOUS
  • Skip to PREVIOUS Message
  • NEXT
  • Skip to NEXT Message
  • LIST
  • Reply to LIST Regarding this Message
  • SENDER
  • Reply to SENDER Regarding this Message
    Time: 06:27:43 PM PST US
    Subject: Re: OV protection circuit design
    From: Charlie England <ceengland7@GMail.com>
    On 3/3/2020 7:55 PM, Pat Little wrote: > On Thu, Feb 27, 2020 at 10:05 AM user9253 <fransew@gmail.com > <mailto:fransew@gmail.com>> wrote: > > <fransew@gmail.com <mailto:fransew@gmail.com>> > > I suggest buying a fuse block that holds 15 or 20 fuses. A > builder once said > to install a fuse block that holds twice as many fuses as you > anticipate > needing, because you will need them. Every single load, no matter how > small, should have its own unique fuse. > Then replace the fuse-links with 30 amp fuses. Doing that will > simplify the > wiring. Looking at Z-20, I suspect the intent was two different > wire sizes, with > one a typo. If a 30 amp fuse is used instead of a fuse-link, then > I would use 22 > AWG for all wires in the field circuit. 22 AWG is good for 7 > amps. It takes 40 > amps to melt 22 wire. > Charlie, the alternator B lead is separate and not shown on the > diagram. > > -------- > Joe Gores > > > I like the simplification of using fuses instead of fuselinks (my > design has 22 fuses so far, another two won't be a problem). And I can > appreciate that if an OV occurs, and the CB trips, the fuse needs to > be big enough to not also blow and deny the pilot the chance to > re-engage the breaker and see if the OV condition repeats itself or not. > > But why 30A? That seems very large as compared to a 5A CB. > > And a separate thought - if the fuse is significantly bigger, and its > sole purpose is to protect the wire between the bus and the CB (am I > interpreting this correctly?), then that segment of wire would need to > be a lot bigger for the fuse to actually protect it. AC 43.13-1B says > a 30A fuse is needed to protect a 10AWG wire - is this a valid reason > for having differing wire sizes in different parts of the circuit? > > Pat My take is a bit different. I really like fusible links for wires that have near zero risk of failure, short (pardon the pun) of a catastrophic fault. A bit of extra work, once. Then it's more compact (it's just part of the wire run, instead of needing another fuse slot), and no risk whatsoever of extra joints, fatigue failure of the link inside an actual fuse, etc. Not saying either approach is 'right'; I just prefer mine. Charlie -- This email has been checked for viruses by Avast antivirus software. https://www.avast.com/antivirus


    Message 4


  • INDEX
  • Back to Main INDEX
  • PREVIOUS
  • Skip to PREVIOUS Message
  • NEXT
  • Skip to NEXT Message
  • LIST
  • Reply to LIST Regarding this Message
  • SENDER
  • Reply to SENDER Regarding this Message
    Time: 06:41:26 PM PST US
    From: "Robert L. Nuckolls, III" <nuckolls.bob@aeroelectric.com>
    Subject: Re: OV protection circuit design
    > >I like the simplification of using fuses instead >of fuselinks (my design has 22 fuses so far, >another two won't be a problem). And I can >appreciate that if an OV occurs, and the CB >trips, the fuse needs to be big enough to not >also blow and deny the pilot the chance to >re-engage the breaker and see if the OV condition repeats itself or not. > >But why 30A? That seems very large as compared to a 5A CB.=C2 The I(square)t operating constant for fuses and breakers of the same RATING are wildly different. Further, the ATC30 fuse is not designed to be used as a LIMITER. Hence, what seems to be overkill is really rather rational. I've crowbared some 5A breakers that would trip an upstream ATC20 fuse. >And a separate thought - if the fuse is >significantly bigger, and its sole purpose is to >protect the wire between the bus and the CB (am >I interpreting this correctly?), then that >segment of wire would need to be a lot bigger >for the fuse to actually protect it. AC 43.13-1B >says a 30A fuse is needed to protect a 10AWG >wire - is this a valid reason for having >differing wire sizes in different parts of the circuit? No, we're emulating a LIMITER . . . i.e. mitigation of a hard fault on the order of hundreds of amps. Same thing that a fusible link does. Just as a 22AWG wire has been DEMONSTRATED to carry 20A continuously without damage, so too will the 14AWG wire gamely step up to continuous loads of 40A or more. However, the thing we're holding at bay is the hard fault that would open the 30A fuse even if the protected feeder were a 22AWG wire. In this case our EXPECTED hard fault is the triggering of a crowbar SCR which generates a predictable fault current in excess of 100A. AC43-13 is a compilation of rules-of-thumb; it's not a properties of materials nor engineering text. It doesn't apply here. Bob . . .


    Message 5


  • INDEX
  • Back to Main INDEX
  • PREVIOUS
  • Skip to PREVIOUS Message
  • NEXT
  • Skip to NEXT Message
  • LIST
  • Reply to LIST Regarding this Message
  • SENDER
  • Reply to SENDER Regarding this Message
    Time: 06:42:59 PM PST US
    From: "Robert L. Nuckolls, III" <nuckolls.bob@aeroelectric.com>
    Subject: Re: OV protection circuit design
    > >I like the simplification of using fuses instead >of fuselinks (my design has 22 fuses so far, >another two won't be a problem). And I can >appreciate that if an OV occurs, and the CB >trips, the fuse needs to be big enough to not >also blow and deny the pilot the chance to >re-engage the breaker and see if the OV condition repeats itself or not. > >But why 30A? That seems very large as compared to a 5A CB.=C2 The I(square)t operating constant for fuses and breakers of the same RATING are wildly different. Further, the ATC30 fuse is not designed to be used as a LIMITER. Hence, what seems to be overkill is really rather rational. I've crowbared some 5A breakers that would trip an upstream ATC20 fuse. >And a separate thought - if the fuse is >significantly bigger, and its sole purpose is to >protect the wire between the bus and the CB (am >I interpreting this correctly?), then that >segment of wire would need to be a lot bigger >for the fuse to actually protect it. AC 43.13-1B >says a 30A fuse is needed to protect a 10AWG >wire - is this a valid reason for having >differing wire sizes in different parts of the circuit? No, we're emulating a LIMITER . . . i.e. mitigation of a hard fault on the order of hundreds of amps. Same thing that a fusible link does. Just as a 22AWG wire has been DEMONSTRATED to carry 20A continuously without damage, so too will the 14AWG wire gamely step up to continuous loads of 40A or more. However, the thing we're holding at bay is the hard fault that would open the 30A fuse even if the protected feeder were a 22AWG wire. In this case our EXPECTED hard fault is the triggering of a crowbar SCR which generates a predictable fault current in excess of 100A. AC43-13 is a compilation of rules-of-thumb; it's not a properties of materials nor engineering text. It doesn't apply here. Bob . . .


    Message 6


  • INDEX
  • Back to Main INDEX
  • PREVIOUS
  • Skip to PREVIOUS Message
  • NEXT
  • Skip to NEXT Message
  • LIST
  • Reply to LIST Regarding this Message
  • SENDER
  • Reply to SENDER Regarding this Message
    Time: 07:53:37 PM PST US
    From: Pat Little <roughleg@gmail.com>
    Subject: Re: OV protection circuit design
    On Tue, Mar 3, 2020 at 7:47 PM Robert L. Nuckolls, III < nuckolls.bob@aeroelectric.com> wrote: > > I like the simplification of using fuses instead of fuselinks (my design > has 22 fuses so far, another two won't be a problem). And I can appreciat e > that if an OV occurs, and the CB trips, the fuse needs to be big enough t o > not also blow and deny the pilot the chance to re-engage the breaker and > see if the OV condition repeats itself or not. > > But why 30A? That seems very large as compared to a 5A CB.=C3=82 > > > The I(square)t operating constant for fuses > and breakers of the same RATING are wildly > different. Further, the ATC30 fuse is not > designed to be used as a LIMITER. Hence, > what seems to be overkill is really rather > rational. I've crowbared some 5A breakers that > would trip an upstream ATC20 fuse. > > > And a separate thought - if the fuse is significantly bigger, and its sol e > purpose is to protect the wire between the bus and the CB (am I > interpreting this correctly?), then that segment of wire would need to be a > lot bigger for the fuse to actually protect it. AC 43.13-1B says a 30A fu se > is needed to protect a 10AWG wire - is this a valid reason for having > differing wire sizes in different parts of the circuit? > > > No, we're emulating a LIMITER . . . i.e. mitigation > of a hard fault on the order of hundreds of amps. > Same thing that a fusible link does. Just as > a 22AWG wire has been DEMONSTRATED to carry > 20A continuously without damage, so too will > the 14AWG wire gamely step up to continuous > loads of 40A or more. > > However, the thing we're holding at bay is > the hard fault that would open the 30A > fuse even if the protected feeder were > a 22AWG wire. In this case our EXPECTED > hard fault is the triggering of a crowbar > SCR which generates a predictable > fault current in excess of 100A. > > AC43-13 is a compilation of rules-of-thumb; > it's not a properties of materials nor > engineering text. It doesn't apply here. > > > Bob . . . > Thanks for the comments. I have revised my drawing - now it looks a lot more like Z-12 preliminary rev NP1 [image: alternator circuits revised.png] Pat


    Message 7


  • INDEX
  • Back to Main INDEX
  • PREVIOUS
  • Skip to PREVIOUS Message
  • NEXT
  • Skip to NEXT Message
  • LIST
  • Reply to LIST Regarding this Message
  • SENDER
  • Reply to SENDER Regarding this Message
    Time: 08:05:07 PM PST US
    From: Paul Zimmer <paul.zimmer00@gmail.com>
    Subject: Battery discharge during normal cruise
    Sorry for the following cut and paste of a previous thread. However after being unable to respond with my follow up post due some unspecified error on the matronics server, (which I thought was something I was doing wrong), I have still been unable to add my follow up to the thread. Hopefully by sending a new email, my follow up will get through. Paul said: I use and monitor two Hall effect current sensors on my RV. One measures the current flow on the "B" lead from the main alternator, and the other measures the current flow to/from the main battery. What doesn't make sense to me is there are periodic and frequent current flows to/from the battery (1 to 5 amps) during normal cruise operations, this during periods of static and relatively light load (12-15 amps) on the electrical system, much smaller than the capacity of the 60A Plane Power alternator. I would expect all power to be supplied directly from the alternator as it is supplying the current at a higher voltage (~14.5v or so) than the battery. These periods of flow to/from the battery are short in duration normally lasting only a few seconds. Is this normal and to be expected, or does it suggest a problem with the internally regulated alternator, or perhaps with the current sensor itself? Any insight explaining what I am seeing will be appreciated. Thanks Bob said: <snip> These periods of flow to/from the battery are short in duration normally lasting only a few seconds. Is this normal and to be expected, or does it suggest a problem with the internally regulated alternator, or perhaps with the current sensor itself? Any insight explaining what I am seeing will be appreciated. The battery's physics reacts to BUS VOLTAGE. Any period battery energy outflow MUST be paired with a drop in bus voltage to something below the battery's present open-circuit voltage. The voltage doesn't have to drop to the battery's natural delivery level (~12.5 volts for SVLA) . . . a battery across an operating bus will support small outflow currents at voltages higher than 12.5. What is your normal bus voltage and do you notice any depression of voltage that corresponds to battery outflow events? Paul said: Bob . . . I can=99t say that I=99ve noticed a bus voltage drop during the se times of battery outflow, but before I say one way or the other, I=99ll need t o pay a little closer attention, and perhaps record the engine monitor parameters during a flight which would allow for an after the fact thorough analysis of what actually went on. I=99ll circle back at a later date. Thank s Paul said: Follow up. I flew for about 30 minutes, during which I recorded the data collected and reported by my GRT EFIS. The sampling rate is about once per second. I converted the data to an EXCEL spreadsheet, and the following are the results. During normal cruise (following start and battery recharge after start), the bus voltage varied from ~13.7 to ~14.0V. The current flow to/from the battery varied both in and out up to a max of 9 amps out all the while battery voltage remains steady at ~13.9V. During these times of battery discharge, load was static (which is to say the load was not deliberately changed). I have a spreadsheet with the data from this flight that was generated from the EFIS, which I don't think I'm able to attach to this Email. Thanks




    Other Matronics Email List Services

  • Post A New Message
  •   aeroelectric-list@matronics.com
  • UN/SUBSCRIBE
  •   http://www.matronics.com/subscription
  • List FAQ
  •   http://www.matronics.com/FAQ/AeroElectric-List.htm
  • Web Forum Interface To Lists
  •   http://forums.matronics.com
  • Matronics List Wiki
  •   http://wiki.matronics.com
  • 7-Day List Browse
  •   http://www.matronics.com/browse/aeroelectric-list
  • Browse AeroElectric-List Digests
  •   http://www.matronics.com/digest/aeroelectric-list
  • Browse Other Lists
  •   http://www.matronics.com/browse
  • Live Online Chat!
  •   http://www.matronics.com/chat
  • Archive Downloading
  •   http://www.matronics.com/archives
  • Photo Share
  •   http://www.matronics.com/photoshare
  • Other Email Lists
  •   http://www.matronics.com/emaillists
  • Contributions
  •   http://www.matronics.com/contribution

    These Email List Services are sponsored solely by Matronics and through the generous Contributions of its members.

    -- Please support this service by making your Contribution today! --